Using a three-way or two-way valve (according to the order)
Using all control equipment from Carel brand
The ability to feed the device from two separate power
sources and a switch between them (optional)
The use of variable speed centrifugal fans
Connecting to the network through the Modbus TCP_IP and SNMP
protocols and the ability to connect through the BACnet protocol
Ability to install a fire alarm sensor (optional)
Ability to install filter dirt warning sensor (optional)
Ability to install a drain pump in the pan (optional)
Ability to install a separate leak sensor (optional) apart
from the pan float sensor
Using a coil with Blue Fin technology for longer life
Using grooved fins to achieve higher coil efficiency
Equipped with humidifier (optional)
Equipped with reheater (optional)
Ability to dehumidify the room with advanced control logic
It can be offered in three models, high and low, female and
facing
Technical specifications and design of single circuit lower female inrom
MRC17D220
|
MRC15D160
|
MRC14D130
|
MRC13D100
|
MRC12D70
|
MRC11D40
|
|
940*3050*2075
|
940*2650*2075
|
940*2200*2075
|
940*1750*2075
|
940*1300*2075
|
940*900*2075
|
Size(H*L*Wmm)
|
214
|
159.3
|
127.2
|
97.4
|
67.4
|
41.5
|
Net cooling capacity(kw)
|
4
|
3
|
2
|
2
|
1
|
1
|
Number of fans
|
16.96
|
12.72
|
8.48
|
8.48
|
4.24
|
4.24
|
Fan motor power
|
16.96+2*6
|
12.72+2*3.75
|
8.48+6
|
8.48+6
|
4.24+3.75
|
4.24+2.25
|
Electrical power (comp+fan+humi)
|
38460(22637)
|
28020(16492)
|
22490(13237)
|
16960(9982)
|
11920(7016)
|
7250(4267)
|
Maximum Air flow
|
2*8
|
2*5
|
8
|
8
|
5
|
3
|
Humidifiler capacity(kg/hr)
|
2way or 3way valve
|
Flow control method
|
6
|
5
|
4
|
|
2
|
1
|
Number of filters
|
82
|
80
|
77
|
76
|
71
|
71
|
Noise levelin 1 meter distance(db)
|
|
|
|
|
|
|
Weight (kg)
|